Sample Container and Preservation Guidelines
Analysis/Constituent | Container | Preservation | Hold Time |
1,2,3 - Trichloropropane | 4x 40ml Amber VOA vials w/HCl | 4x 40ml Amber VOA vials w/HCl + Travel Blanks (4 vials filled with lab blank water) If Chlorinated; neutralize in 1-250ml Amber bottle with Ascorbic Acid, then pour into VOA Vials w/HCl. Cool, 4 C | 14 days - cold |
Sampling Instructions:A Chain of Custody(COC)form, listing all samples, date and time sampled, and analysis requested should be filled out by the Sampler. This COC form should accompany the samples to the testing laboratory. Click Here For Environmental Sampling Procedures |
For More Environmental Services Information Contact:
Environmental Customer Services Phone: (805)392-2000 envcustservices@fglinc.com